- Demonstration of Knowledge
- Details:
- Food manager certificate is lacking. Provide thee department with a copy of a valid food manager certificate within 60 days (employee to take exam on Feb.17).
- Comment:
- All food employees shall have adequate knowledge of and be trained in food safety as it relates to their assigned duties. (113947) Food facilities that prepare, handle or serve non-prepackaged potentially hazardous food, shall have an employee who has passed an approved food safety certification examination. (113947-113947.1) Any food handler hired after June 1, 2011 shall obtain a Food Handler Card within 30 days (113948).
- Hot and Cold Potable Water Not Available
- Details:
- 3 comp sink and mop sink hot water is at 113F. Provide hot and cold water t these sinks with hot water at a minimum of 120F.
- Comment:
- An adequate, protected, pressurized, potable supply of hot water and cold water shall be provided at all times. (113953(c), 114099.2(b) 114101(a), 114189, 114192, 114192.1, 114195)
- Approved / Sufficient Ventilation and Lighting
- Details:
- Shattterproof covering is lacking for light in walk-in. Provide. Operator to provide me with proof that light bulb is shatter proof.
- Comment:
- Exhaust hoods shall be provided to remove toxic gases, heat, grease, vapors and smoke and be approved by the local building department. Canopy-type hoods shall extend 6" beyond all cooking equipment. All areas shall have sufficient ventilation to facilitate proper food storage. Toilet rooms shall be vented to the outside air by a screened openable window, an air shaft, or a light-switch activated exhaust fan, consistent with local building codes. (114149, 114149.1) Adequate lighting shall be provided in all areas to facilitate cleaning and inspection. Light fixtures in areas where open food is stored, served, prepared, and where utensils are washed shall be of shatterproof construction or protected with light shields. (114149.2, 114149.3, 114252, 114252.1)
- Floors, Walls, Ceilings
- Details:
- Clean and Maintained
- Comment:
- Observed debris and grease accumulation on floor near deep fryer. Clean.
|
02/05/2016 | Reinspection |
- Critical: Food Contact Surfaces Sanitized or Warewashing Sanitization (corrected on site)
- Details:
- Observed employee washing dishes without sanitizing. Ok, corrected sanitizer and water added to 3 comp. at "sanitize" compartment of sink.
- Comment:
- All food contact surfaces of utensils and equipment shall be clean and sanitized. (113984(e), 114097, 114099.1, 114099.4, 114099.6, 114101 (b-d), 114105, 114109, 114111, 114113, 114115 (a, b, d), 114117, 114125(b), 114135, 114141)
- Demonstration of Knowledge
- Details:
- Food manager certificate is lacking. Provide the department with a copy of a valid food manager certificate within 60 sixty days.
- Comment:
- All food employees shall have adequate knowledge of and be trained in food safety as it relates to their assigned duties. (113947) Food facilities that prepare, handle or serve non-prepackaged potentially hazardous food, shall have an employee who has passed an approved food safety certification examination. (113947-113947.1) Any food handler hired after June 1, 2011 shall obtain a Food Handler Card within 30 days (113948).
- Handwashing Facilities Supplied and Accessible
- Details:
- Soap is lacking at single use dispenser at hand sink across from 3 comp. Soap temporarily provided. Provide soap in single use dispenser.
- Comment:
- Handwashing soap and towels or drying device shall be provided in dispensers dispensers shall be maintained in good repair. (113953.2) Adequate facilities shall be provided for hand washing, food preparation and the washing of utensils and equipment. (113953, 113953.1, 114067(f))
- Hot and Cold Potable Water Not Available
- Details:
- Hot water at 3 comp is at 118F and mopsink is at 115F. Provide at 120F or higher.
- Comment:
- An adequate, protected, pressurized, potable supply of hot water and cold water shall be provided at all times. (113953(c), 114099.2(b) 114101(a), 114189, 114192, 114192.1, 114195)
- Equipment/Utensils Approved and in Good Repair
- Details:
- Observed a large crack in cheese grater attachment that attaches to large mixer. Provide equipment that is free of cracks.
- Comment:
- All utensils and equipment shall be fully operative and in good repair. (114175). All utensils and equipment shall be approved, installed properly, and meet applicable standards. (114130, 114130.1, 114130.2, 114130.3, 114130.4, 114130.5, 114132, 114133, 114137, 114139, 114153, 114155, 114163, 114165, 114167, 114169, 114177, 114180, 114182)
- Approved / Sufficient Ventilation and Lighting
- Details:
- Shatterproof covering is lacking for light in walk-in. Provide.
- Comment:
- Exhaust hoods shall be provided to remove toxic gases, heat, grease, vapors and smoke and be approved by the local building department. Canopy-type hoods shall extend 6" beyond all cooking equipment. All areas shall have sufficient ventilation to facilitate proper food storage. Toilet rooms shall be vented to the outside air by a screened openable window, an air shaft, or a light-switch activated exhaust fan, consistent with local building codes. (114149, 114149.1) Adequate lighting shall be provided in all areas to facilitate cleaning and inspection. Light fixtures in areas where open food is stored, served, prepared, and where utensils are washed shall be of shatterproof construction or protected with light shields. (114149.2, 114149.3, 114252, 114252.1)
- Thermometers Provided/Accurate/Easily Visible
- Details:
- Thermometer is lacking fro 3 door reach in under pizza prep refrigerator and front display refrigerator near register. Provide
- Comment:
- An accurate easily readable metal probe thermometer suitable for measuring temperature of food shall be available to the food handler. A thermometer +/- 2 #F shall be provided for each hot and cold holding unit of potentially hazardous foods and high temperature warewashing machines. (114157, 114159)
- Plumbing Maintained
- Details:
- Approved Back Flow Device
- Comment:
- 3 comp sink faucet continually runs even when faucet handel is turned in the "off" position. Provide so that faucet is in proper working order.
- Floors, Walls, Ceilings
- Details:
- Clean and Maintained
- Comment:
- Observed debris on flooring behind pizza oven and on flooring near deep fryer. Observed debris on wall and grease accumulation on electrical receptacle on wall between deep fryer and pizza prep table. Clean
|
01/15/2016 | Routine |
- Handwashing Facilities Supplied and Accessible
- Comment:
- Handwashing soap and towels or drying device shall be provided in dispensers dispensers shall be maintained in good repair. (113953.2) Adequate facilities shall be provided for hand washing, food preparation and the washing of utensils and equipment. (113953, 113953.1, 114067(f))
|
01/14/2015 | Reinspection |
- Handwashing Facilities Supplied and Accessible
- Comment:
- Handwashing soap and towels or drying device shall be provided in dispensers dispensers shall be maintained in good repair. (113953.2) Adequate facilities shall be provided for hand washing, food preparation and the washing of utensils and equipment. (113953, 113953.1, 114067(f))
- Hot and Cold Holding Temperatures
- Comment:
- Potentially hazardous foods shall be held at or below 41/ 45°F or at or above 135°F. (113996, 113998, 114037, 114343(a))
- Food Storage/Display Properly labeled
- Comment:
- Food shall be stored in approved containers and labeled as to contents. Food shall be stored at least 6" above the floor on approved shelving. (114047, 114049, 114051, 114053, 114055, 114067(h), 114069 (b))
- Approved / Sufficient Ventilation and Lighting
- Comment:
- Exhaust hoods shall be provided to remove toxic gases, heat, grease, vapors and smoke and be approved by the local building department. Canopy-type hoods shall extend 6" beyond all cooking equipment. All areas shall have sufficient ventilation to facilitate proper food storage. Toilet rooms shall be vented to the outside air by a screened openable window, an air shaft, or a light-switch activated exhaust fan, consistent with local building codes. (114149, 114149.1) Adequate lighting shall be provided in all areas to facilitate cleaning and inspection. Light fixtures in areas where open food is stored, served, prepared, and where utensils are washed shall be of shatterproof construction or protected with light shields. (114149.2, 114149.3, 114252, 114252.1)
- Toilet Facilites Clean/ Supplied/ Maintained
- Comment:
- Toilet facilities shall be maintained clean, sanitary and in good repair. Toilet rooms shall be separated by a well-fitting self-closing door. Toilet tissue shall be provided in a permanently installed dispenser at each toilet. The number of toilet facilities shall be in accordance with local building and plumbing ordinances. Toilet facilities shall be provided for patrons: in establishments with more than 20,000 sq ft. establishments offering on-site liquor consumption. (114250, 114250.1, 114276)
- Floors, Walls, Ceilings
- Details:
- Clean and Maintained
|
12/24/2014 | Routine |
- Handwashing Facilities Not Supplied and Accessible
- Comment:
- Handwashing soap and towels or drying device shall be provided in dispensers dispensers shall be maintained in good repair. (113953.2) Adequate facilities shall be provided for hand washing, food preparation and the washing of utensils and equipment. (113953, 113953.1, 114067(f))
- Improper Hot and Cold Holding Temperatures
- Comment:
- Potentially hazardous foods shall be held at or below 41/ 45°F or at or above 135°F. (113996, 113998, 114037, 114343(a))
- Equipment/Utensils Not Approved/Installed/Cleaned
- Comment:
- All utensils and equipment shall be fully operative and in good repair. (114175). All utensils and equipment shall be approved, installed properly, and meet applicable standards. (114130, 114130.1, 114130.2, 114130.3, 114130.4, 114130.5, 114132, 114133, 114137, 114139, 114153, 114155, 114163, 114165, 114167, 114169, 114177, 114180, 114182)
- Toilet Facilites Not Clean/ Supplied/ Maintained
- Comment:
- Toilet facilities shall be maintained clean, sanitary and in good repair. Toilet rooms shall be separated by a well-fitting self-closing door. Toilet tissue shall be provided in a permanently installed dispenser at each toilet. The number of toilet facilities shall be in accordance with local building and plumbing ordinances. Toilet facilities shall be provided for patrons: in establishments with more than 20,000 sq ft. establishments offering on-site liquor consumption. (114250, 114250.1, 114276)
- Premises: Not Clean/Litter Free
- Details:
- Not Vermin-Proof
- Floors, Walls, Ceilings
- Details:
- Not Clean and Maintained
- Signs Not Posted
- Details:
- Last Inspection Rpt Unavailable
|
01/14/2014 | Routine |
- Handwashing Facilities Not Supplied and Accessible
- Comment:
- Handwashing soap and towels or drying device shall be provided in dispensers dispensers shall be maintained in good repair. (113953.2) Adequate facilities shall be provided for hand washing, food preparation and the washing of utensils and equipment. (113953, 113953.1, 114067(f))
- Signs Not Posted
- Details:
- Last Inspection Rpt Unavailable
|
02/27/2013 | Reinspection |
- Critical: Handwashing Facilities Not Supplied and Accessible
- Comment:
- Handwashing soap and towels or drying device shall be provided in dispensers dispensers shall be maintained in good repair. (113953.2) Adequate facilities shall be provided for hand washing, food preparation and the washing of utensils and equipment. (113953, 113953.1, 114067(f))
- Critical: Improper Hot and Cold Holding Temperatures (corrected on site)
- Comment:
- Potentially hazardous foods shall be held at or below 41/ 45°F or at or above 135°F. (113996, 113998, 114037, 114343(a))
- Handwashing Facilities Not Supplied and Accessible
- Comment:
- Handwashing soap and towels or drying device shall be provided in dispensers dispensers shall be maintained in good repair. (113953.2) Adequate facilities shall be provided for hand washing, food preparation and the washing of utensils and equipment. (113953, 113953.1, 114067(f))
- Improper Hot and Cold Holding Temperatures (corrected on site)
- Comment:
- Potentially hazardous foods shall be held at or below 41/ 45°F or at or above 135°F. (113996, 113998, 114037, 114343(a))
- Hot and Cold Potable Water Not Available
- Comment:
- An adequate, protected, pressurized, potable supply of hot water and cold water shall be provided at all times. (113953(c), 114099.2(b) 114101(a), 114189, 114192, 114192.1, 114195)
- Food Unprotected from Contamination During Storage
- Comment:
- All food shall be separated and protected from contamination. (113984 (a, b, c, d, f), 113986, 114060, 114067(a, d, e, j), 114069(a, b), 114077, 114089.1 (c), 114143 (c))
- Equipment/Utensils/Linens: Improper Storage / Use
- Comment:
- All clean and soiled linen shall be properly stored non-food items shall be stored and displayed separate from food and food-contact surfaces. (114185.3 - 114185.4) Utensils and equipment shall be handled and stored so as to be protected from contamination. (114074 - 114075, 114081, 114119, 114121, 114161, 114178, 114179, 114083, 114185, 114185.2, 114185.5)
- Thermometers Not Provided/Accurate/Easily Visible
- Comment:
- An accurate easily readable metal probe thermometer suitable for measuring temperature of food shall be available to the food handler. A thermometer +/- 2 #F shall be provided for each hot and cold holding unit of potentially hazardous foods and high temperature warewashing machines. (114157, 114159)
- Signs Not Posted
- Details:
- Last Inspection Rpt Unavailable
|
02/04/2013 | Routine |
No violation noted during this evaluation. | 02/24/2012 | Reinspection |